UPS APC Smart SC1000 with NUT / Linux


APC Smart SC1000

image (C) APC

Hi! Here’s another UPS review 😉 I am not an UPS tester by profession, but this topic seems to be around me recently, caused by various opportunities. This time I am playing with APC Smart SC1000 tower/rack-mount unit, and it’s nut interoperation.

The unit comes with two data cables, one is RS-232 to RS-232 and the other is RS-232 (ups side) to USB (host side). The USB device is detected as:

067b:2303 Prolific Technology, Inc. PL2303 Serial Port

So it is actually a serial device. The driver to use is apcsmart with one significant setting:

port = /dev/ttySx
port = /dev/ttyUSBx
port = /dev/serial/by-id/usb-Prolific_Technology_Inc._USB-Serial_Controller-if00-port0

Remember that the serial device must be accessible by the uid which nut driver is running with. Try an udev rule.

Here’s the upsc output:

# upsc apc1000
battery.alarm.threshold: 0
battery.charge: 012.0
battery.charge.restart: 00
battery.date: 10/06/11
battery.runtime: 600
battery.runtime.low: 120
battery.voltage: 24.44
battery.voltage.nominal: 024
device.mfr: APC
device.model: Smart-UPS SC1000
device.serial: 5S1141T08304
device.type: ups
driver.name: apcsmart
driver.parameter.pollinterval: 2
driver.parameter.port: /dev/serial/by-id/usb-Prolific_Technology_Inc._USB-Serial_Controller-if00-port0
driver.version: 2.4.3
driver.version.internal: 2.03
input.frequency: 50.00
input.quality: FF
input.sensitivity: H
input.transfer.high: 253
input.transfer.low: 208
input.transfer.reason: simulated power failure or UPS test
input.voltage: 242.0
input.voltage.maximum: 242.0
input.voltage.minimum: 242.0
output.voltage: 242.0
output.voltage.nominal: 230
ups.delay.shutdown: 060
ups.delay.start: 000
ups.firmware: 737.3.I
ups.id: theups
ups.load: 011.0
ups.mfr: APC
ups.mfr.date: 10/06/11
ups.model: Smart-UPS SC1000
ups.serial: 5S1141T08304
ups.status: OL
ups.test.interval: 1209600
ups.test.result: NO

Here’s the upsrw output:

# upsrw apc1000
[battery.date]
Battery change date
Type: STRING
Value: 10/06/11

[ups.id]
UPS system identifier
Type: STRING
Value: theups

And here’s the upscmd output:

# upscmd -l apc1000
Instant commands supported on UPS [apc1000]:calibrate.start - Start run time calibration
calibrate.stop - Stop run time calibration
load.off - Turn off the load immediately
shutdown.return - Turn off the load and return when power is back
shutdown.stayoff - Turn off the load and remain off
test.battery.start - Start a battery test
test.battery.stop - Stop the battery test
test.failure.start - Start a simulated power failure
test.panel.start - Start testing the UPS panel

Tested and working commands: shutdown.return, test.battery.start, test.failure.start, test.panel.start; other commands not tested – I have learned a lesson recently.

And as before, here are a few graphs displaying charging and discharging data with ups.load about 13-15:

Fig. 1 Charging - 12 hours - data with battery.runtime

Fig. 1 Charging - 12 hours - data with battery.runtime

The runtime seems to stabilize after about 6 hours, however battery voltage is further increasing slowly.

Fig. 2 Charging - 12 hours - focus on battery.charge and battery.voltage

Fig. 2 Charging - 12 hours - focus on battery.charge and battery.voltage

A discharge cycle has run for about 54 minutes and it was interrupted manually – battery voltage was going really low and I did not want to risk it’s life. However I did one or two discharge cycles before this plotted version, and the UPS successfully shut-off itself with a higher battery.voltage. Therefore I could have been safe, but did not want to take any risk anyway.

UPS started to signal low-battery (LB) after 39 minutes (~2350 sec), but lasted at least 15 minutes after. This may or may not be your case, my previous run proved about 5 minutes on LB before automatic shut-off.

Fig. 3 - Discharging - data with battery.runtime

Fig. 3 - Discharging - data with battery.runtime

Fig. 4 Discharging - focus on battery.charge

Fig. 4 Discharging - focus on battery.charge

Fig. 5 Discharging - focus on battery.voltage

Fig. 5 Discharging - focus on battery.voltage

To summarize – it is a very good UPS, behaves reliably and it’s interoperation with nut is just excellent with apcsmart driver.

Advertisement

What do you think?

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out /  Change )

Twitter picture

You are commenting using your Twitter account. Log Out /  Change )

Facebook photo

You are commenting using your Facebook account. Log Out /  Change )

Connecting to %s




Enter your email address to follow this blog and receive notifications of new posts by email.

Join 51 other subscribers

Marcin Gałkowski

Seasoned admin, Linux hacker, Android fan, Gentoo enthusiast. Doing digital audio on Linux when time permits. At work: IT Team Lead (+labs, +datacenters...)

Latest Tweets

BTC tip jar:

1HprotPu2zi8v8hFZBqVfcTYL7ZYVYBruo

%d bloggers like this: